Problems kept coming with chiller

Follow
HVACTIME

Had an issue with a York YK centrifugal tripping on a vein position switch alarm. After doing some calibrations on the compressor prv I was able to get the switch to make. Then I figured out that the pull down settings were not configured which was leading to vsd motor overcurrent. This was one of those were one thing definitely led to another. Centrifugal compressors are a critical piece for HVAC technician to begin learning chillers and getting HVAC training.

Tool Recommendations
https://geni.us/HVACTIME (Amazon)

Get tech support and training at hvactimetx.com

You can contact me at [email protected]

Support the channel through,
https://venmo.com/code?user_id=316085...
Zelle @ [email protected]

As an Amazon Associate I earn from qualifying purchases

00:00 York YK Vane Motor Switch
01:30 PRV Calibration
02:08 What is PRV
04:37 YK Prelube Oil Management
05:21 Centrifugal Approach during Pulldown
06:07 VSD High Motor Current
06:54 YK Pulldown Configuration
08:29 Reset VSD Logic Board Fault