It was never so easy to get YouTube subscribers
Get Free YouTube Subscribers, Views and Likes

How to Size a Pressure Tank

Follow
R.C. Worst & Co., Inc.

I’m going to show you how easy it is to size a pressure tank!

Sizing Chart Link: https://www.rcworst.com/Shared/conten...

Choosing the proper tank for your pumping system will greatly reduce the risk of premature pump failure. When it comes to pressure tanks, bigger is almost always better.
Larger tank = larger drawdown (actual amount of water stored)larger drawdown means longer run time and therefore less cycles, extending the life of the motor. Most manufacturers recommend a minimum run time of one minute for efficient motor cooling. One HP and larger pumps require longer run times.
To determine the proper size of tank, there are three factors to consider:
1. Pump ow rate in gallons per minute
2. Desired run time of the pump
3. Cutin and cutout psi of the pressure switch
From these factors you can determine drawdown needed with the following equation:
Pump ow rate X run time = tank drawdown capacity required.
Tank drawdown capacity is the minimum amount of water stored and/or delivered by the pressure tank between pump shutoff and pump restart. This should not be confused with “tank volume.” For example, a precharged tank with a tank volume of 20 gallons has only ve
to seven gallons drawdown capacity depending on the cutin / cutout (on/off) setting of the pressure switch. Pumps with ow rates (capacities) up to 10 GPM should have a tank with a minimum of one gallon drawdown capacity for each GPM
delivered by the pump.
Example: 10 GPM pump = 10 gallon “drawdown”.
Pump ow rates from 11 to 20 GPM should have tank drawdowns approximately 1.5 times the GPM rating.
For example, 20 GPM X 1.5 = 30 gallon “drawdown”.
Pump ow rates above 20 GPM should have tank drawdowns approximately two times the GPM rating and multiple tanks should be considered.

Sizing Chart Link: https://www.rcworst.com/Shared/conten...


If you need more information or assistance with products, call 855.329.4519 or email [email protected] to speak with an industry expert. Thanks for watching!

Add us to your professional network: https://www.linkedin.com/companybeta...

Follow us on Twitter:   / rcworst  

Like us on Facebook:   / rcworst  

For more industry videos visit our YouTube Channel:    / @rcworstwater  

Check out our website: https://www.rcworst.com/

We are a distributor of pumps, packaged pumping systems, onsite wastewater treatment equipment, onsite wastewater treatment systems, and custom electrical control panels for water and wastewater applications, water well supplies, drilling supplies, and water treatment equipment.

posted by myrtle31cc